eQuest Latent Heat Recovery
Topic: Parametrically simulating latent heat recovery in eQuest requires specifying a number of items in coordination to obtain meaningful results.
Following is model for a simple one-system one-zone building. The enthalpy wheel is only of interest in the Seattle climate due to a tight temperature & humidity control requirement (73°F ± 2°F and 50% RH ± 3%) for the building in occasional operating modes.
- Envelope improvements including reduced infiltration from an estimated 0.1 to 0.01 CFM/SF were modeled as the first parametric run,
- Increased temperature and humidity precision as the second, and
- Heat recovery using the enthalpy exchanger as the third.
$ This example models a sensible-latent enthalpy wheel air-to-air heat
$ exchanger (EW A2A HX) as the energy recovery equipment.
"EL1 Exhibit Hall Sys" = SYSTEM
TYPE = SZRH
HEAT-SOURCE = HOT-WATER
ZONE-HEAT-SOURCE = HOT-WATER
BASEBOARD-SOURCE = NONE
SIZING-RATIO = 1
$ The following parameter may be spec'd in precision control mode (PCM)
HUMIDIFIER-TYPE = ELECTRIC
MAX-SUPPLY-T = 95
MIN-SUPPLY-T = 55
$ The following number is changed to 53 in PCM
MAX-HUMIDITY = 80
$ The following number is changed to 47 in PCM
MIN-HUMIDITY = 10
$ The following parameter results in 1 OACH at 50% turndown, see zone flow below.
MIN-OUTSIDE-AIR = 0.32
$ The following parameter is changed to FIXED-FRACTION in PCM, which
$ caps the capacity of the heat wheel at MIN-OUTSIDE-AIR, in this
$ case 32% of 50,000 or 16,000 CFM
OA-CONTROL = OA-TEMP
$ Change the following keyword to YES in heat recovery parametric run; all other
$ heat recovery parameters are ignored when set to NO for the baseline case:
RECOVER-EXHAUST = NO
$ Full OSA economizer is used when 8precision control is not required;
$ the following number is reduced to 0.5 in precision control parametric run,
$ which effectively limits the capacity of the ERV to 50% of the main unit:
FAN-SCHEDULE = "S1 Sys1 (VAVS) Fan Sch"
$ change to VFD from default, unless VFD needs justification...
FAN-CONTROL = SPEED
SUPPLY-STATIC = 3.5
RETURN-STATIC = 1.125
$ change to VFD from default, unless VFD needs justification...
FAN-EIR-FPLR = "Fan-Pwr-fPLR-w/VFD"
$ change to VFD from default, unless VFD needs justification...
RETURN-FAN-CONTR = SPEED
$ change to VFD from default, unless VFD needs justification...
RETURN-EIR-FPLR = "Fan-Pwr-fPLR-w/VFD"
REHEAT-DELTA-T = 30
HW-LOOP = "Hot Water Loop"
CHW-LOOP = "Chilled Water Loop"
$ The following parameter may be spec'd in the precision control parametric run
HUMIDIFIER-LOC = IN-AIR-HANDLER
CONTROL-ZONE = "EL1 Exhibit Hall Zn"
ERV-RECOVER-TYPE = ENTHALPY-WHEEL
$ The following six parameters are the default values, hardcoded here
$ to provide a sense of their relative magnitudes:
ERV-SENSIBLE-EFF = 0.76
ERV-SEN-FILM-RES = 0.7
ERV-SEN-FILM-EXP = 0.5
ERV-LATENT-EFF = 0.74
ERV-LAT-FILM-RES = 0.7
ERV-LAT-FILM-EXP = 0.4
$ Remaining parameters are characteristic of a sidecar enthalpy wheel:
ERV-RUN-CTRL = OA-EXHAUST-DH
ERV-RECOVER-MODE = OA-HEAT/COOL
ERV-CAP-CTRL = MODULATE-HX
ERV-FANS = SELF-CONTAINED
ERV-OA-STATIC = 0.7
ERV-EXH-STATIC = 0.5
ERV-FROST-CTRL = USE-CAP-CTRL
..
"EL1 Exhibit Hall Zn" = ZONE
TYPE = CONDITIONED
$ The following number allows the VAV system to turn-down by 50%
MIN-FLOW-RATIO = 0.5
MIN-FLOW-SCH = "EL1 Bldg Occup Sch"
ASSIGNED-FLOW = 50000
$ The following number is changed to 72 in the precision control parametric run
DESIGN-HEAT-T = 70
HEAT-TEMP-SCH = "S1 Sys1 (VAVS) Heat Sch"
$ The following number is changed to 75 in the precision control parametric run
DESIGN-COOL-T = 80
COOL-TEMP-SCH = "S1 Sys1 (VAVS) Cool Sch"
SIZING-OPTION = FROM-LOADS
SPACE = "EL1 Exhibit Hall Spc"
..
The annual energy cost results are essentially as expected. Compared to the...
- Baseline condition using 100% outside air economizer, the
- Envelope improvements save a bit, the
- Precision control costs additionally, and
- Enthalpy recovery reduces energy costs attractively.
This simplifies operation, allowing to the system to function in heat recovery mode all year round, under all occupancy and ambient conditions.