Tuesday, November 07, 2006

Standard Energy Efficiency Measures

Topic: Energy Efficiency Measures (EEMs) that may prove cost-effective in the context of typical ELCCA projects.

  • Daylighting
  • Heat recovery
  • Envelope improvements from Code Minimum up to ELCCA Prescriptives
    • Roof
    • Wall
    • Window & door
  • Demand ventilation
    • CO2 zone sensor control for large volumes, or
    • Lighting occupancy sensor control for offices and classrooms
      • If the electrical engineer is providing occupancy sensors for lighting control in the classrooms and possibly office areas, then interlocking the outside air damper operation to close when the lights are commanded off is a relatively simple energy saver.
      • Estimating the value of this EEM is variable depending on the school -- obviously high schools and colleges with classrooms that aren't necessarily used all day will have a higher diversity and thus stand to save more energy.
      • However if electrical is providing the occupancy sensor, then the marginal cost of interlocking for HVAC control should be minimal.
      • Given actual elementary school schedules for assemblies, lunch hours, recesses, field trips, and early dismissal a potential for savings exists -- but quantifying it is little more difficult.
  • Improved boiler efficiency
    • Typically improved from an 80% baseline to 85% or 88%
  • Improved lighting utilization per unit area over code specified maximum

Monday, October 30, 2006

Washington State Utility Rates

Topic: Provide quick access to current utility rates in Washington state.

Notes:
(1) PSE Electric Schedules: 7 Residential, 31 General Commercial
(2) PSE Gas Schedules: 23 Residential, 31 General Commercial, 36 Special Educational

Thursday, August 31, 2006

Qualified Software for Tax Credits

Topic: Energy-Efficient Commercial Building Tax Deduction under Internal Revenue Service Code 179D. Reference IRS Notice 2006-52 dated June 2, 2006.


Consultants can help facility owners take advantage of the above tax deductions. As of this writing the qualified software list includes the latest versions of EnergyPlus, Trace 700, and Carrier HAP. There is a rumor on the boards that eQUEST is in in the process of becoming certified.
 

Wednesday, August 09, 2006

Carrier HAP Displacement Ventilation

Not to be outdone, the folks at Carrier HAP software support also have some recommendations for modeling displacement ventilation systems:

1. TRACE has a feature that models the return air plenum as a separate space. This lets you define the size of the plenum and heat going into and out of it. The calculate a load for it as if it was a room and also calculate its temperature. The seem to be recommending you use this feature to model the upper stratified zone of the room as a "plenum space" and assign portions of the room loads like lights, etc.. to the plenum space.

In HAP we don't have an equivalent feature. But you could define a return air plenum and assign part of your lighting, wall and roof loads to the plenum as a way of derating the heat going to the occupied zone in the space. You still need a way to deal with people and plug loads. Perhaps use the schedules to derate these heat gains, or just specify derated sqft/person and W/sqft to begin with. What you'll miss is the portion of these heat gains that goes into the upper zone. And you'll miss the kWh consumption for plug loads if you're doing an energy analysis (could put those back in via miscellaneous energy in the building inputs). Don't know if TRACE lets you put people and office equipment inside a plenum space. Maybe they have a problem with people and plugs too.

2. On the system side it sounds like they recommend modeling a constant volume AHU that uses a bypass so you have part of the air going thru the cooling coil and part going through a bypass and the two streams mixing downstream. Something equivalent in HAP might be this:

a. Choose a 3-Deck Multizone system. In cooling mode it mixes neutral (untreated) with cold deck air in the proper proportions to get the proper SAT to meet the load.

b. Specify the central cooling with 55 F SAT and constant supply temperature control.

c. You'll want to use user-defined sizing on the sizing tab so you can directly specify the supply airflow. This airflow should be sufficient to meet the peak zone sensible load with a 60 to 65 F supply temperature at the supply diffuser. To figure out what this airflow for 60 to 65 F SAT is to begin with, you may need to run the system once with SAT specfied as 60 to 65 F. Then go back and edit the air system, change the SAT to 55 F and switch to user defined sizing to put in the airflow. Then run calculations a second time. The result is the supply temperature at the diffuser will be 60 F or above, and it will be a mixture of 55 F cold deck air plus untreated neutral deck air.

We recommend looking carefully at the results like the component loads on the System Design Load Summary and the system operating details on System Psychrometrics to get a feel for whether everything is working the way you intend it to, and is representing what you think displacement ventilation behavior should be.

Best Regards,
Carrier HAP Support