Trace 700 Notes
Topic: Notes for using Trace 700 in the ELCCA analysis
- Domestic hot water: Trace applies an occupancy schedule to and calculates a number for domestic hot water usage, but please note the following
- Inputs parameters for domestic hot water consumption are in the Base Utility/Miscellaneous Accessory tab of the 'Create Plants' module.
- Calculated domestic hot water consumption is shown as a line item on the Equipment Energy Consumption report.
- But domestic hot water totals are not included in the Energy Cost Budget, Energy Consumption Summary, Monthly Energy Consumption, or Monthly Utility Cost reports.
- Therefore it is necessary to add the domestic hot water consumption numbers to the HVAC totals in the ELCCA report spreadsheet.